In low-voltage switchgear, the part that decides whether a fault stays contained is rarely the most expensive one. It is usually a partition, a barrier or a support sitting a few millimetres from where an arc terminates - and the material behind it is increasingly a polyester glass mat laminate rather than a phenolic paper board.
GPO-3, produced by Friend Group as grade F622 and internationally designated UPGM203, is an unsaturated polyester glass mat laminate hot-pressed from non-alkali glass fibre mat and resin paste. Its published specification is built around tracking and arc behaviour rather than mechanical strength: comparative tracking index of at least 600 V, tracking and erosion class 1B 2.5, UL94 V-0 at 1 mm, and a thermal rating of Class B.
This article explains why the arc-adjacent position changed, what the mat construction contributes, which figures in the datasheet actually decide a design, and where GPO-3 should not be used.
What Changed: DC Arcs Punish the Tracking Path
An AC arc extinguishes at a current zero crossing, twice per cycle. A DC arc has no such natural interruption, so the energy that a barrier surface absorbs during a fault lasts longer and deposits more carbon. As photovoltaic strings move to 1500 V DC, as battery energy storage cabinets multiply inside the same switch rooms, and as vehicle platforms shift to 800 V, the insulating parts around contactors and breakers see a harsher duty than the AC-only equipment those parts were originally developed for.
The failure mechanism is not a simple puncture. It is a progressive one: an arc or a surface discharge leaves a carbonised path, the path becomes slightly conductive, the next event concentrates along it, and the tracking channel grows until the creepage distance that the design assumed no longer exists. Materials that look equivalent on a dry breakdown test separate sharply on this path. That is why comparative tracking index, measured to IEC 60112, and arc resistance, measured to ASTM D495 or its IEC equivalent, carry more weight in an arc-adjacent position than dielectric strength does.
Humidity compounds the problem. Outdoor cabinets, coastal installations and washdown areas all put condensation on the same surfaces that must survive an arc. A material with a high initial tracking index but a porous or moisture-absorbing surface will drift downward over service life, and the drift is what the maintenance interval has to absorb.
What the Glass Mat Construction Contributes
GPO-3 is not a woven laminate. The reinforcement is a non-woven glass mat, a random laid felt of chopped strands, impregnated with unsaturated polyester resin paste containing fillers, flame retardants and stabilisers, then consolidated under heat and pressure into a rigid sheet.
Random fibre orientation changes behaviour in three useful ways. In-plane properties are more uniform, because there is no warp and weft direction to create a weak axis. There is no weave print-through on the surface, so a thin barrier has a smoother, more resin-rich face - which matters for tracking, since a resin-rich surface resists carbonisation better than one where glass strands sit proud. And the mat construction tolerates filler loading well, which is how flame retardancy and arc resistance are dialled in without wrecking processability.
The trade-off is mechanical. A mat laminate gives up some flexural and impact performance against a woven glass fabric laminate of similar resin content, which is why GPO-3 is specified for barriers and supports rather than for structural load paths. The published datasheet also quotes arc resistance above 180 seconds to ASTM D495, a figure that no phenolic paper grade reaches, and that is the number most breaker designers check first.
Where GPO-3 Belongs, and Where It Does Not
The strongest fit is anywhere an arc is expected to terminate within centimetres: phase barriers and arc chutes in moulded case and air circuit breakers, arc barriers and baffles in contactors, insulating supports and shrouds around busbars, and support structures inside SVC and SVG cabinets where both voltage and harmonic currents are present.
It also suits parts that need moderate mechanical strength combined with electrical safety at medium temperature - covers, mounting plates, terminal supports and spacers in equipment that runs inside Class B limits.
It is the wrong choice in three situations. Continuous hotspot temperature above 130 °C calls for a higher-class polyester such as UPGM205 in its Class F or Class H versions. Thin, precise structural parts that carry load - slot wedges, end plates, machined brackets - are better served by an epoxy glass laminate such as 3240 or FR4, which trades some arc resistance for stiffness and dimensional stability. And where a closed three-dimensional geometry has to be produced in volume, a moulding compound such as BMC or SMC will beat machining a sheet, because the cost curves cross once tooling can be amortised.
Sheet, Punch Grade or Moulding: Where the Cost Line Sits
There are three routes from the same material family to a finished part, and the choice is economic before it is technical.
Machining from sheet suits low and medium volumes, complex outlines, and any design still moving. Standard sheet sizes are 1010×2010 mm and 1250×2500 mm, which allows several barriers to be nested per sheet. The limitation is that every hole and radius is a separate operation, and thin sections need support to avoid chipping.
A punch grade, supplied as F622CP, suits flat parts with a stable design and annual volumes high enough to justify tooling. Blanking is fast and repeatable, the material is formulated for the process, and the per-part cost falls sharply - but the design must be frozen before the die is cut.
Moulding compounds such as BMC and SMC suit three-dimensional geometry, metal insert encapsulation and parts where the shape cannot be cut from a flat sheet. Tooling cost is the entry ticket; the crossover usually arrives when a part would otherwise need several machined pieces assembled together.
For a breaker programme, the practical sequence is to prototype in machined sheet, freeze the design, then move to punching or moulding once volumes are known. Doing it the other way round - tooling first - is the most common source of expensive redesign.
GPO-3 Against Phenolic Paper and Epoxy Glass
The three material families that compete for the same barrier position behave very differently, and the differences are structural rather than incremental.
| Material | Reinforcement and resin | Strength in this position | Watch-out |
|---|---|---|---|
| GPO-3 (F622 / UPGM203) | Glass mat, unsaturated polyester | Tracking and arc resistance, flame retardancy, uniform in-plane properties | Lower flexural strength than woven glass grades; Class B only |
| Phenolic paper (PFCP201 / NEMA X) | Paper, phenolic resin | Low cost, good machinability, adequate dielectric performance in dry conditions | Carbonises and tracks more readily under arcing; moisture sensitive; dark colour limits inspection |
| Epoxy glass (3240 / EPGC201, FR4 / EPGC202) | Woven glass cloth, epoxy | Mechanical strength, dimensional stability, dielectric margin | Less arc resistance than a mat polyester at equal cost; machining dust is more abrasive |
The practical rule that follows: choose by the failure mode the position is exposed to. If the risk is an arc tracking across a surface, the mat polyester wins. If the risk is mechanical - vibration, torque, a part that must hold a tolerance for a decade - the woven epoxy wins. If the risk is cost in a dry, protected, low-energy position, phenolic paper still has a place.
What to Ask Before You Qualify a Barrier Material
Datasheets describe materials; qualification tests suppliers. For an arc-adjacent part the questions are specific.
Ask which test method produced the arc resistance figure - ASTM D495 and IEC 61621 are not identical, and a number quoted without a method is not usable in a design review. Ask for the tracking index with the specimen thickness and the test solution stated, since CTI is thickness and contamination dependent. Confirm that the UL yellow card lists the exact grade, colour and thickness being purchased, because recognition is granted per construction, not per trade name.
Ask for the retained insulation resistance after humidity conditioning at the thickness in use, rather than the standard four-millimetre absorption figure. Ask how colour is controlled between lots, since barrier colour is often used as an inspection cue on the line. For machined parts, ask about edge quality and dust extraction, because polyester glass dust is an irritant and a poorly supported thin section will chip at the edges.
Finally, for rail, renewable and automotive programmes, request batch traceability back to the press lot. The requirement increasingly appears in customer audits, alongside carbon reporting that now reaches down to material suppliers.
Frequently Asked Questions
What is GPO-3? GPO-3 is an unsaturated polyester glass mat laminate, designated UPGM203 in IEC terms and produced by Friend Group as grade F622. It is hot-pressed from non-alkali glass fibre mat impregnated with polyester resin paste and additives, and is used mainly for insulating barriers, arc chutes and supports in switchgear and control equipment.
Is GPO-3 the same as UPGM203? They describe the same material family. UPGM203 is the IEC type designation; GPO-3 is the NEMA-style designation widely used in North America.
Friend Group's F622 is specified as similar to both, and is manufactured to ISO, NEMA, IEC, DIN and JIS requirements.
What is GPO-3's tracking index and arc resistance? The published specification gives a comparative tracking index of at least 500 V to IEC 60112, tracking and erosion class 1B 2.5, and arc resistance above 180 seconds to ASTM D495 - the property set that makes the grade suitable for arc-adjacent positions.
What thermal class is GPO-3, and what is used above it? F622 is Class B, rated for 130 °C continuous service.
For Class F or Class H duty, UPGM205 is available in F623 (Class F) and F623HH (Class H) versions, both based on the same polyester glass mat system.
Can GPO-3 be supplied as punched or moulded parts rather than sheet? Yes. F622CP is a punch grade intended for blanked flat parts, and the same material family extends into BMC and SMC moulding compounds for three-dimensional components and insert encapsulation. Selection between them is driven by volume and geometry rather than by electrical performance.
Is GPO-3 suitable for outdoor and humid installations? The grade is formulated for good electrical performance under high humidity and is flame retardant to UL94 V-0 at 1 mm. For outdoor cabinets, the design should still be validated with a humidity-conditioned dielectric test at the thickness in use, and the tracking index confirmed against the pollution degree assumed in the creepage calculation.
About Beijing Friend Group
Founded in 1996 and headquartered in the Beijing Yizhuang Economic and Technological Development Zone, Friend Group produces epoxy glass, phenolic paper, phenolic cotton, polyester and silicone laminates, together with laminated rods, tubes, moulding compounds and machined insulating components. Manufacturing runs across a 70,000+ m² materials plant in Hebei and an 8,000+ m² deep-processing base in Jiangsu, supported by a joint laboratory with the Institute of Chemistry, Chinese Academy of Sciences established in 2004 and a Beijing Enterprise Technology Center since 2007. The company is one of the drafting units of China's national standards for electrical insulating materials and thermosetting moulding plastics, holds ISO 9001, ISO 14001 and ISO 45001 certification, and supplies customers including ABB, Siemens, Schneider Electric, Alstom, General Motors, Goldwind and CRRC.
For barrier and arc-chamber parts, send the drawing, the working voltage, the pollution degree and the expected fault energy through the contact page and the technical team will match grade and thickness to the geometry. Full data for the grade is listed on the GPO-3 (F622) polyester glass mat product page; related options include the F622CP punch grade, UPGM205 Class F and Class H versions, BMC and SMC moulding compounds, and the epoxy glass alternatives covered in our earlier analysis of 800 V traction motor insulation requirements.